Manual 2100-594
Page 17 of 19
Speed
W48A23
W48L23
W60A23
W60L23
High High
ESP
(Inch
H20)
Dry
Coil
Wet
Coil
Dry
Coil
Wet
Coil
0.0 1850 1800 2080 2015
0.1 1775 1725 2020 1960
0.2 1685 1640 1925 1865
0.3 1590 1550 1870 1815
0.4 1495 1460 1755 1705
0.5 1400 1365 1660 1610
Model
Rated
CFM
Rated
ESP
Recommended
Airow Range
W48A23
W60A24
1550
1770
.30
.40
1750 - 1350
1950 - 1425
Model
Dimension
A
W48A2 / W48L2
W60A2 / W60L2
1.75"
TROUBLESHOOTING
FIGURE 8
FAN BLADE SETTING
TABLE 2
FAN BLADE DIMENSION
REMOVAL OF FAN SHROUD
1. Disconnect all power to the unit.
2. Remove the screws holding both grilles, one on
each side of unit, and remove grilles.
3. Remove screws holding fan shroud to condenser
and bottom. Nine (9) screws.
4. Unwire condenser fan motor.
5. Slide complete motor, fan blade, and shroud
assembly out the left side of the unit.
6. Service motor/fan as needed.
7. Reverse steps to reinstall.
R-410A
REFRIGERANT CHARGE
This unit was charged at the factory with the quantity of
refrigerant listed on the serial plate. AHRI capacity and
efciency ratings were determined by testing with this
refrigerant charge quantity.
The following pressure tables show nominal pressures
for the units. Since many installation specic situations
can affect the pressure readings, this information should
only be used by certied technicians as a guide for
evaluating proper system performance. They shall not
be used to adjust charge. If charge is in doubt, reclaim,
evacuate and recharge the unit to the serial plate charge.
TABLE 3
RATED CFM AND ESP
TABLE 4
INDOOR BLOWER PERFORMANCE CFM @ 230V
"A"
AIRFLOW
MIS-1724
FAN BLADE SETTING DIMENSIONS
Shown in Figure 8 is the correct fan blade setting for
proper air delivery across the outdoor coil. Refer to
Table 2 for unit specic dimension.
Any service work requiring removal or adjustment
in the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.
Rated CFM & ESP on High Speed tap with 14 x 28
return air lter grille